UTILITIES
Its fireproof nature means that it can be used for many different applications: to build interior dividing walls, technical premises, self-supporting ceilings, etc., in premises classified as having a high fire risk.
MAIN COMPONENTS
INSULATION:
135 Kg/m3 density rock wool, with A1 fire reaction classification.
COATING:
Steel Sheet slightly ribbed, galvanized and pre-lacquered polyester (25 µ) with a peelable protective film.White colour. Food safe quality.
OTHER FINISHINGS MADE TO ORDER:
Plastisol 100µ, Skimplate 120µ, AISI 304 stainless steel, other thicknesses, other colours, etc.
135 Kg/m3 density rock wool, with A1 fire reaction classification.
COATING:
Steel Sheet slightly ribbed, galvanized and pre-lacquered polyester (25 µ) with a peelable protective film.White colour. Food safe quality.
OTHER FINISHINGS MADE TO ORDER:
Plastisol 100µ, Skimplate 120µ, AISI 304 stainless steel, other thicknesses, other colours, etc.
FIRE CONCEPTS
FIRE RESISTANCE:
The capacity of a structural element to comply for a
certain length of time with fire stability, impermeability
or fire integrity, thermal insulation and/or other required
functions, specified in the testing regulations.
REACTION TO FIRE:
Products response contributing with its own
decomposition to a fire it is exposed to, under specified
conditions.
The capacity of a structural element to comply for a
certain length of time with fire stability, impermeability
or fire integrity, thermal insulation and/or other required
functions, specified in the testing regulations.
REACTION TO FIRE:
Products response contributing with its own
decomposition to a fire it is exposed to, under specified
conditions.
FIRE RESISTANCE
The fire resistance of a structural element is specified by the European Standard UNE-EN-13501-2, which defines the fire resistance on the basis of some criterions:
· BEARING CAPACITY
· INTEGRITY
· INSULATION
The European Standards defining fire resistance testing for non-bearing walls are UNE-EN 1363, UNE-EN 1364-1 and UNE-EN 1364-2.
· BEARING CAPACITY
· INTEGRITY
· INSULATION
The European Standards defining fire resistance testing for non-bearing walls are UNE-EN 1363, UNE-EN 1364-1 and UNE-EN 1364-2.
REACTION TO FIRE
Products reaction to fire is defined by the UNE-EN 13501-1
Standard. Materials are classified as follows:
· BY THEIR COMBUSTION CAPACITY: A1, A2, B, C, D, ETC.
· BY THEIR SMOKE PRODUCTION: S1, S2, S3.
· BY THE INFLAMMABLE PARTICLES THEY RELEASE: D0, D1,D2.
Standard. Materials are classified as follows:
· BY THEIR COMBUSTION CAPACITY: A1, A2, B, C, D, ETC.
· BY THEIR SMOKE PRODUCTION: S1, S2, S3.
· BY THE INFLAMMABLE PARTICLES THEY RELEASE: D0, D1,D2.
Fireproof Panel, KIDE