Η φωτογραφία ενδέχεται να είναι ενδεικτική – Καλέστε μας για επιβεβαίωση.
MINI “ELEBAR” Ø60 DECOMPRESSION VALVE FOR FREEZING ROOMS
Pressure Relief (Decompression) Valves for Refrigerated Rooms for Freezing Applications
Pressure relief valves are designed to equalize the internal pressure of the room with the external ambient pressure through ventilation. The absence of these components may cause various problems in the joints of the cold rooms, ice formation, etc.
Method for calculating the required air quantity for equalizing the internal and external pressure:
Q = K × V × Δt
Where:
Q = Required air quantity in litres per minute (L/min), K = constant 3.66, V = refrigerated room volume in cubic metres (m³), and Δt = maximum temperature variation inside the room during a one-minute period.
Example: Cold-storage room (positive-temperature application) with a volume of 60 m³ and a temperature variation during 1 minute of 2°C. Result: 3.66 × 60 × 2 = 439 L/min, required air quantity.
Login to see prices
2102280384 - 2102286268